Description

Fluke 1746/ EUS Three-Phase Power Quality Logger – Choice of Kit

The Fluke 1746/ EUS Power Quality Logger is optimised for basic power quality logging and will record all the necessary parameters for this purpose. It can be used to help engineers and technicians make critical power quality and energy decisions pertaining to electrical network planning. This power quality analyser and logger can also be used to conduct energy saving studies.

This model is suitable for use in Europe, the UK and US; it is available in three kits that vary in regards to the included iFlex current probes:

  • FLUKE 1746/B/EUS – Fluke 1746/EUS Three-Phase Power Quality Logger WITHOUT Probes
  • FLUKE 1746/15/EUS – Fluke 1746/EUS Three-Phase Power Quality Logger with 1500A iFlex Probes
  • FLUKE 1746/30/EUS –  Fluke 1746/EUS Three-Phase Power Quality Logger with 3000A iFlex Probes 

Measurement Functions

As mentioned above, the Fluke 1746/ EUS Three-Phase Power Quality Logger can be used to capture all the relevant parameters for conducting energy saving studies and planning electrical networks. This inspection, diagnostic and maintenance tool’s eclectic measurement capabilities also make it suitable for carrying out quality-of-service surveys, quantifying energy usage and troubleshooting power distribution systems. This instrument is able to capture and save the following parameters:

  • Voltage
  • Current
  • Power
  • Power factor
  • Frequency
  • Energy forward/ reverse
  • Peak demand
  • THD
  • Flicker
  • Voltage and current harmonics (up to the 50th)
  • Unbalance
  • Rapid voltage change events
  • Interharmonics (up to the 50th)
  • Inrush current

Additionally, the Fluke 1746/ EUS Three-Phase Power Quality Logger is able to record voltage events such as dips, swells, interruptions, current and inrush current. It can also measure all three voltage and current phases as well as neutral current when used with three-phase and neutral voltage test leads and four flexible current probes (NOT included with the Fluke 1746/B model).

The extensive measurement and logging capabilities of the Fluke 1746/ EUS Three-Phase Power Quality Logger make it suitable for assessing power quality in accordance with EN 50160 and IEEE 519 standards; additionally, this instrument is compliant with IEC 61000-4-30 Class A Edition 3. It can be used to perform measurements at various positions along the power installation, from the service entrance to the substation to the load.

Memory and Data Download

Logged parameters are saved to the Fluke 1746/ EUS Three-Phase Power Quality Logger’s internal memory; this instrument has the capacity to save in excess of twenty logging sessions.

Moreover, to ensure that measurement trends are complete, the Fluke 1746/ EUS Three-Phase Power Quality Logger will automatically log a number of power parameters.

Recorded data can be downloaded to a PC using a USB interface, an Ethernet connection or via Wi-Fi. Transferring data to a PC via Wi-Fi allows the user to view measurement trends remotely and in real-time, thereby facilitating quick decision-making whilst reducing the need for PPE as the engineer/ technician is able to remain outside of dangerous environments.

Further to this, as the Fluke 1746/ EUS Three-Phase Power Quality Logger includes two USB ports, data can be saved directly to a USB memory stick whilst the instrument transfers information to a connected PC or laptop via a USB interface. As a result, data can be saved and viewed without removing the Fluke 1746/ EUS Three-Phase Power Quality Logger from the field.

Analysis and Reporting

The Fluke 1746/ EUS Three-Phase Power Quality Logger is supplied with Fluke’s Energy Analyse Plus Software. This program allows the user to view data that has been transferred from the Fluke 1746/ EUS Three-Phase Power Quality Logger to a PC either by a wired or wireless connection.

Additionally, the Fluke Energy Analyse Plus Software can be used to analyse transferred data; it is capable of investigating every detail of the energy consumption and power quality state-of-health. The user can select a particular parameter to create a customised view thereby facilitating advanced data correlation. Additionally, it is possible to perform day/day, week/week and hour/hour comparisons. Data can be exported in PQDIF and NeQual formats, allowing for further analysis using third-party software.

Moreover, downloaded data can be used to create EN 50160, IEEE 519, GOST 33073 reports. These reports can be generated at the touch of a button and their templates may be altered in order to keep up with evolving standards.

Ergonomic, Rugged Design

Physical Design

As mentioned above it is possible to transfer data using a variety of methods and it is also possible to connect multiple current probes to the Fluke 1746/ EUS Three-Phase Power Quality Logger. As a result, the Fluke 1746/ EUS Three-Phase Power Quality Logger is equipped with a number of ports (including AUX, I/O, USB and Ethernet ports) all of which have an IP65 rating ensuring that they are protected from dust and moisture ingress when not in use.

Further to this, the Fluke 1746/ EUS Three-Phase Power Quality Logger has the highest safety rating in the industry (600V CAT IV / 1000V CAT III), making it suitable for applications at service entrances and downstream.

Also adding to the practicality of the Fluke 1746/ EUS Three-Phase Power Quality Logger is its ability to be powered by the circuit-under-investigation and, to this end, includes a wide power range: it will go from 100V to 500V automatically.

Alternatively, the Fluke 1746/ EUS Three-Phase Power Quality Logger can be powered via a wall line cord or by its lithium-ion battery. The lithium-ion battery is able to provide up to four hours of power per charge, ensuring that it is able to withstand temporary power disruptions.

The Fluke 1746/ EUS Three-Phase Power Quality Logger’s small dimensions (23cm x 18cm x 5.4cm) makes it suitable for use in tight spaces whilst its ability to be secured using a standard chain or other security instrument means that it is protected from theft and can be left in the field.

Accessories

The Fluke 1746/ EUS Three-Phase Power Quality Logger’s supplied accessories also make it suitable for use in small, rugged places. The 2m test lead allows the user to access difficult-to-reach conductors as do the flexible, IP65, thin current probes (NOT included with the Fluke 1746/B).

Furthermore, these flexible current probes feature a wide range (probe dependent) ensuring a high accuracy despite the application. They can be connected to the Fluke 1746/ EUS Three-Phase Power Quality Logger separately thereby ensuring maximum flexibility.

System Interface

The Fluke 1746/ EUS Three-Phase Power Quality Logger’s verification feature will ensure that accessories such as flexible current probes, clamps and test leads are connected correctly. The power button will shine an amber light when connections are faulty, changing to green when they have been corrected. This feature is able to digitally correct unsatisfactory connections without the user having to disconnect any of the components.

In addition to this, the Fluke 1746/ EUS Three-Phase Power Quality Logger is able to recognise, scale and power connected clamps and/or probes and will do this automatically upon connection. This ensures that the Fluke 1746/ EUS Three-Phase Power Quality Logger and the connected probes and/or clamps are configured correctly enabling accurate and reliable measurements.

Configuring the Fluke 1746/ EUS Three-Phase Power Quality Logger for each application is made easy due to the inclusion of a quick, guided, graphical PC-application setup interface.

The Fluke 1746/ EUS Three-Phase Power Quality Logger is an accurate and adaptable three-phase power quality analyser with an array of measurement capabilities for basic power quality logging.

 Fluke 1746/ EUS Three-Phase Power Quality Logger Key Features

  • Optimised for basic power quality logging
  • Records all the necessary parameters for basic power quality logging
  • Provides the necessary data for making critical energy and power quality decisions
  • Suitable for electrical network planning applications
  • Can be used to conduct energy saving studies
  • Suitable for carrying out quality-of-service surveys, quantifying energy usage and troubleshooting power distribution systems
  • Suitable for use in Europe, the UK and the US
  • Available in three kits that vary in regards to the included iFlex current probes
  • Can capture an array of power parameters
  • Voltage
  • Current
  • Power
  • Power factor
  • Frequency
  • Energy forward/ reverse
  • Peak demand
  • THD
  • Flicker
  • Voltage and current harmonics (up to the 50th)
  • Unbalance
  • Rapid voltage change events
  • Interharmonics (up to the 50th)
  • Inrush current
  • Records voltage events such as dips, swells, interruptions, current and inrush current
  • Use with three-phase and neutral voltage test leads and four flexible current probes to measure all three voltage and current phases and neutral current
  • Assess power quality in accordance with EN 50160 and IEEE 519 standards
  • Compliant with IEC 61000-4-30 Class A Edition 3
  • Can be used to perform measurements at various positions along the power installation
  • Log parameters at the service entrance, substation or at the load
  • Internal memory: capacity to store in excess of twenty logging sessions
  • Automatically logs a number of parameters to ensure measurement trends are complete
  • Download data to a PC via a USB interface, Ethernet connection or via Wi-Fi
  • Wi-Fi connectivity allows the user to view data remotely and in real-time
  • Wi-Fi connectivity means the user is able to remain outside of dangerous environments
  • Includes two USB ports
  • Data can be downloaded directly to a USB memory stick
  • Supplied with Fluke Energy Analyse Plus Software
  • Fluke Energy Analyse Plus Software can be used to view measurements remotely, analyse data and create reports
  • Fluke’s Energy Analyse Plus Software can be used to investigate every detail of the energy consumption and power quality state-of-health
  • Create a customised view of a single power parameter for advanced data correlation using the Fluke Energy Analyse Plus Software
  • View day/day, week/week and hour/hour comparisons using the included software
  • Create EN 50160, IEEE 519, GOST 33073 reports at the touch of a button using the included software
  • Report templates can be altered to accommodate evolving standards
  • Data can be exported in PQDIF and NeQual formats using the Fluke Energy Analyse Plus Software
  • IP65 ports
  • Highest safety rating in the industry: 600V CAT IV / 1000V CAT III
  • Suitable for applications at service entrances and downstream
  • Can be powered by the circuit-under-investigation
  • Wide power range: will go from 100V to 500V automatically
  • Can be powered using a wall line cord or by the lithium-ion battery
  • The lithium-ion battery can provide up to four hours of power per charge
  • Small size for use in tight spaces: 23cm x 18cm x 5.4cm
  • Can be secured using a standard chain or another security instrument
  • 2m test lead facilitates access to difficult-to-reach components
  • Flexible, thin, IP65 current probes (NOT included with the Fluke 1746/B) also facilitate access to awkwardly placed components
  • Wide probe range (probe dependent) ensuring high accuracy regardless of the application
  • Up to four probes can be connected separately ensuring maximum flexibility
  • Intelligent verification feature ensures that clamps, probes and test leads are connected correctly
  • Incorrect connections are indicated by an amber light
  • Correct connections are indicated by a green light
  • The intelligent verification feature will digitally correct faulty connections without the user having to disconnect any components
  • Automatically recognises, scales and powers connected clamps and/or probes
  • Quick, guided, graphical PC-application setup interface
  • An accurate and adaptable three-phase power quality analyser with an array of measurement capabilities for basic power quality logging

What’s Included?

  • Your Choice of Fluke 1746/ EUS Three-Phase Power Quality Logger Kit (see below)
ItemsFLUKE1746/B/EUSFLUKE1746/15/EUSFLUKE1746/30/EUS
Fluke 1746/EUS Three-Phase Power Quality LoggerXXX
1500A iFlex Current Probes (60cm)X
3000A iFlex Current Probes (60cm)X
USB StickXXX
USB CableXXX
3PHVL-1730 3-Phase + neutral voltage test leadXXX
Test lead set red/black 0.18 mXXX
Test lead set red/black 1.5 mXXX
Alligator clips444
173x/174x Soft CaseXXX
Cable marker kitXXX
MP1-3R/1B-Magnet Probe 1 set (3 red, 1 black)111

Fluke 174X Three-Phase Power Quality Loggers Technical Specifications

Please note that the Fluke 1746/EUS Three-Phase Power Quality Loggers are part of Fluke’s range of 174X Three-Phase Power Quality Loggers; the table below details the technical specifications for all the models included in this range.

Specifications
Accuracy
ParameterRangeMaximum ResolutionIntrinsic Accuracy at Reference Conditions (% of Reading +% of Range)
Voltage1000 V0.1 V±0.1 % of nominal voltage 1, 2
Current: Direct inputi17xx-flex 1500IP 24 1500 A150 A0.01 A (min. 1.5A)3±(1% + 0.02%)
1500 A0.1 A
i17xx-flex 3000IP 24 3000 A300 A0.01 A (min. 3.0 A)3±(1% + 0.03%)
3000 A0.1 A
i17xx-flex 6000IP 36 6000 A600 A0.01 A (min. 6.0 A)3±(1.5% + 0.03%)
6000 A0.1 A
i40s-EL clamp4 A1 mA±(0.7% + 0.02%)
40 A10 mA
Frequency42.5 Hz to 69 Hz0.01 Hz±(0.1%)2
Auxiliary input±10 V dc0.1 mV±(0.2% + 0.02%)
Voltage min/max1000 V0.1 V±0.2 % of nominal input voltage1
Current min/maxDefined by accessoryDefined by accessory±(5% + 0.2%)
THD on voltage1000%0.10%± 2.5%
THD on current1000%0.10%± 2.5%
Voltage harmonics 2nd to 50th1000 V0.1 V≥ 1 V: ±5% of reading
< 1 V: ±0.05V
Current harmonics 2nd to 50thDefined by accessoryDefined by accessory≥ 3% of current range: ±5% of reading
< 3% of current range: ±0.15% of range
Flicker PLT, PST0 to 200.015%
Current probe accuracy
ParameterInfluence quantity/iFlex1500IP-24iFlex3000IP-24iFlex6000IP-36i40S-EL
150 A / 1500 A300 A / 3000 A600 A / 6000A4 A / 40 A
Active Power PPF ≥ 0.991.2% + 0.005%1.2% + 0.0075%1.7% + 0.0075%1.2% + 0.005%
Active Energy Ea
Apparent power S0 ≤ PF ≤ 11.2% + 0.005%1.2% + 0.0075%1.7% + 0.0075%1.2% + 0.005%
Apparent Energy Eap
Reactive power Q0 ≤ PF ≤ 12.5% of measured apparent power
Reactive Energy Er
Power Factor PF±0.025
Displacement Power
Factor DPF/cosΦ
Additional uncertainty in% of rangeVP-N>250 V0.015%0.023%0.023%0.015%
1 In the range of 100 V … 500 V; also known as Udin
2 0 °C … 45 °C: Intrinsic accuracy x 2, outside of 0 °C … 45 °C: Intrinsic accuracy x 3
3 Consult operators manual for details
Reference conditions:
Environmental: 23 °C ± 5 °C, instrument operating for at least 30 minutes, no external electrical/magnetic field, RH <65 %
Input conditions: Cosφ/PF=1, Sinusoidal signal f=50 Hz/60 Hz, power supply 120 V/230 V ±10 %.
Current and power specifications: Input voltage 1 ph: 120 V/230 V or 3 ph wye/delta: 230 V/400 V
Input current: I > 10 % of I range
Primary conductor of clamps or Rogowski coil in center position
Temperature coefficient: Add 0.1 x specified accuracy for each degree C above 28 °C or below 18 °C
Electrical Specifications
Power Supply
Voltage range100 V to 500 V using safety plug input when powering from the measurement circuit
100 V to 240 V MA-C8 and using standard power cord (IEC 60320 C7)
Power consumptionMaximum 50 VA (max. 15 VA when powered using MA-C8 adapter)
Efficiency≥ 68.2% (in accordance with energy efficiency regulations)
Maximum no-load consumption< 0.3 W only when powered using IEC 60320 input
Mains power frequency50/60 Hz ±15%
BatteryLi-ion 3.7 V, 9.25 Wh, customer-replaceable
On-battery runtimeTypically 4 hours
Charging time< 6 hours
Data Acquisition
Resolution16-bit synchronous sampling
Sampling frequency10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input signal frequency50/60 Hz (42.5 to 69 Hz)
Circuit types1-Φ, 1-Φ IT, split phase, 3-Φ delta, 3-Φ wye, 3-Φwye IT, 3-Φ wye balanced, 3-Φ Aron/Blondel (2-element delta), 3-Φ delta open leg, currents only (load studies)
Data storageInternal flash memory (not user replaceable)
Memory sizeTypical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events
Basic Interval
Measured parametersVoltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy
Averaging intervalUser selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Averaging time min/max valuesVoltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms)
Demand Interval (Energy Meter Mode)
Measured parametersEnergy (Wh, varh, VAh), PF, maximum demand, cost of energy
IntervalUser selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Power Quality Measurements
Measured parameterVoltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, voltage interharmonics, TID V, current interharmonics, TID A, Flicker, Mains Signaling, under/over deviation
Averaging interval10 min for all parameters
2 hrs (long term Flicker PLT)
150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT)
Individual harmonics2nd to 50th harmonic
Grouping according to IEC 61000-4-7 user configurable depending on application: Sub-grouped (harmonics + interharmonics), grouped or harmonic bins only
Interharmonics1st to the 50th interharmonic
Total harmonic distortionCalculated on 50 voltage harmonics
EventsVoltage: dips, swells, interruptions, current: inrush current
1748: mains signaling, transients (low frequency)
Triggered recordingsRMS profile: Full cycle RMS updated every half cycle of voltage and current up to 11 s (URMS1/2 according to IEC 61000-4-30)
Waveform of voltage and current up to 200 ms, 10/12 cycles
Mains signaling: 10/12 cycle RMS recording of the configured frequencies up to 120s
InrushRMS profile based on 1/2 cycle RMS steady state triggering
FlickerIn accordance with IEC 61000-4-15 and IEEE 1453
Mains signalingTwo user defined frequencies up to 3 kHz
PQ HealthSummarizes power quality measurements in one table. Detailed data available for each parameter
EN 50160Compliance with standard
Programmable PQ limitsEnables user defined limits for local standards compliance
Standards Compliance
HarmonicsIEC 61000-4-7: Class 1
IEEE 519 (short time and very short time harmonics)
Power qualityIEC 61000-4-30 Class A, IEC 62586-1, IEC 62586-2 (PQI-A-PI device)
PowerIEEE 1459
Power quality complianceEN 50160
SafetyGeneral: IEC 61010-1: Pollution Degree 2
Measurement: IEC 61010-2-033: CAT IV 600 V / CAT III 1000 V
Power Supply: Overvoltage Category IV, Pollution Degree 2
Li-ion Battery: IEC 62133
Interfaces
USB-AFile transfer via USB flash drive, firmware updates, max. supply current: 120 mA
WiFiFile transfer and remote control via direct connection or WiFi infrastructure
BluetoothRead auxiliary measurement data from Fluke Connect® 3000 series modules (requires supported USB to BLE or WiFi/BLE adapter, check for availability)
USB-miniData download device to PC
Current Inputs
Number of inputs4 (3 phases and neutral), mode selected automatically for attached sensor
Input voltageClamp input: 500 mVrms/50 mVrms; CF 2.8
Rogowski coil input: 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4 all at nominal probe range
Range1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 IP 24
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 IP 24
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 IP 36
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
Bandwidth42.5 Hz – 3.5 kHz
Scaling1:1 and variable
Auxiliary Inputs
Number of inputs2 (Analog with auxiliary adapter, or up to 2 BLE devices simultaneously)
Input range0 to ± 10 V dc, or 0 to ± 1000 V dc (with optional adapter), 1 reading/s
Scale factorFormat: mx + b (gain and offset) user configurable
Displayed unitsUser configurable (7 characters, for example, °C, psi, or m/s)
Wireless Bluetooth connection (check for availability)
Number of inputs2
Supported modulesFluke Connect® 3000 series
Acquisition1 reading/s
Environmental Specifications
Operating temperature-25 °C to +50 °C (-13 °F to 122 °F)1
Storage temperatureWithout battery: -25 °C to +60 °C (-13 °F to 140 °F), with battery: -20 °C to +50 °C (−4 °F to 122 °F)
Operating humidityIEC 60721-3-3: 3K6:
-25 °C to +30 °C (-13 °F to +86 °F): ≤ 100 %
40 °C (104 °F): 55 %
50 °C (122 °F): 35 %
Operating Altitude2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Storage altitude12,000 m
EnclosureIEC 60529: IP50
IEC 60529: IP65 with IP65 rated voltage connector
VibrationIEC 60721-3-3 / 3M2
Electromagnetic compatibility (EMC)EN 61326-1: Industrial CISPR 11: Group 1, Class A
IEC 61000-6-5 Power station environment
Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment)
USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103
General Specifications
WarrantyTwo-years (battery not included)
Accessories: one-year
Calibration cycle: two-years
Dimensions23.0 cm x 18.0 cm x 5.4 cm (9.1 in x 7.1 in x 2.1 in)
WeightInstrument: 1 kg (2.2 lb)
Tamper protectionAccept securing cables (max. Φ 6mm)
1Warm up the product to -10 °C (+14 °F) before you power the unit on
Flexible Current Probe Specifications
Specificationsi17XX-FLEX1.5KIPi17XX-FLEX3KIP
Measuring range1 to 150 A ac/10 to 1500 A ac1 to 300 A ac 10 to 3000 A ac
Probe cable length610 mm (24 in)610 mm (24 in)
Probe cable diameter7.5 mm (0.3 in)7.5 mm (0.3 in)
Weight170 g (0.38 lb)170 g (0.38 lb)
Minimum bending radius38 mm (1.5 in)
Nondestructive current100 kA (50/60 Hz)
Temperature coefficient over
operating temperature range
0.05 % of reading/°C (0.028 % of reading/°F)
Working voltage1000 V CAT III, 600 V CAT IV
Output cable length2.0 m (6.5 ft)
Probe cable materialTPR
Weight115 g
Probe cable materialTPR
Coupling materialPOM + ABS/PC
Output cableTPR/PVC
Operating temperature-20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F)
Temperature, non-operating-40 °C to +80 °C (-40 °F to 176 °F)
Relative humidity, operating15% to 85% non-condensing
IP ratingIEC 60529: IP65
WarrantyOne-year

Fluke 174X Three-Phase Power Quality Loggers Comparison Table

Functions 1742 Power Quality Loggers1746 Power Quality Loggers1748 Power Quality Loggers
Voltage, current, power, power factor, frequencyXXX
Energy forward/reverseXXX
Peak DemandXXX
THDXXX
Voltage and current harmonics (to 50th)1XX
FlickerXXX
Unbalance1XX
Rapid voltage change events1XX
Interharmonics (to 50th)1XX
Dips, swells, interruption and transient events tables1XX
Mains signalingXX
Inrush current1XX
Transients (low frequency)/Waveform deviation events2X
Recording 1742 Power Quality Loggers1746 Power Quality Loggers1748 Power Quality Loggers
TrendXXX
Waveform snapshots2X
RMS profile2X
Communication 1742 Power Quality Loggers1746 Power Quality Loggers1748 Power Quality Loggers
EthernetXXX
USB (mini B)XXX
WiFi download Instrument to deviceXXX
Wifi download via WiFi hub (requires registration)OptOptOpt
Included accessories1742 Power Quality Loggers1746 Power Quality Loggers1748 Power Quality Loggers
Flexible current probenot /B versionnot /B versionnot /B version
USB stickXXX
USB cableXXX
3PHVL-1730 3-Phase + neutral voltage test leadXXX
Test lead set red/black 0.18 mXXX
Test lead set red/black 1.5 mXXX
Alligator clips444
173x/174x Soft CaseXXX
Cable marker kitXXX
MP1-3R/1B-Magnet Probe 1 set (3 red, 1 black)Opt11
174x-Hanger KitOptOptX

🚚 Testersmans Shipping Policy

Free Mainland GB Delivery Over £150

We offer free delivery on most mainland Great Britain orders over £150 (ex VAT).
This applies across England, Wales, and most of Scotland, excluding certain remote or offshore postcodes.

If your order total falls just short of £150, or you’re a returning customer, feel free to contact us — we may be able to offer a discount code or delivery workaround.
📞 01945 738112 | ✉️ [email protected]


📦 UK Delivery Options

We work with both Royal Mail and DHL to offer reliable and flexible delivery across the UK:

  • Royal Mail – Best suited for lighter parcels and for customers in remote regions, including the Highlands, Islands, and Northern Ireland.
  • DHL – Ideal for most mainland UK orders, providing fast, tracked delivery and excellent reliability for time-sensitive shipments.

Our checkout system automatically displays the available delivery services for your postcode and order weight, ensuring you always see the most suitable options.

Note: Heavy, bulky, or freight-only orders will be charged separately.
Our website is designed for quick, transactional purchases rather than bulk or palletised orders.
Please contact us in advance for a tailored freight quotation if your order falls into this category.


⏱ Dispatch & Delivery Timing

We aim to dispatch all in-stock orders promptly, but delivery depends on both when you order and which service you select.

  • UK orders: placed by 2:00 PM Monday–Friday are usually dispatched the same day.
  • International orders: placed by 2:00 PM Monday–Thursday are usually dispatched the same day.

Orders placed after these times are processed the next working day. This means delivery may occur the following day or later, depending on the courier and service selected.

Once dispatched, your chosen delivery service determines how quickly your parcel arrives:

  • Standard services We use Royal Mail Tracked 24 or DHL Parcel as our ‘Standard’ services. They are not guaranteed to arrive next working day.
  • Premium services (e.g. Royal Mail Special Delivery or DHL by Noon) offer guaranteed delivery windows.

If your order is time-sensitive, we strongly recommend choosing a guaranteed service or contacting us before ordering to confirm availability.

Please note: For logistical reasons, we may occasionally adjust the delivery method selected at checkout. For example, smaller items may be better suited to letterbox-friendly packaging or may be at greater risk of delay or loss via certain services. We actively monitor courier and postal service disruptions—including strikes and delays—and may modify shipping arrangements to help ensure timely and secure delivery.


📅 Busy Periods & Delays

We always aim to dispatch promptly, but delivery times may be affected by:

  • Seasonal demand (e.g. Christmas, bank holidays, or industry shutdowns)
  • Courier network delays outside our control
  • Supplier lead times or calibration requirements for certain equipment

If your delivery is time-critical, please contact us before ordering so we can confirm stock and courier availability.


🌍 International Shipping

We ship worldwide using UPS Express Saver® and other trusted global courier partners. All international shipments are tracked and generally dispatched Monday to Thursday to ensure smooth customs clearance and transit.

Estimated delivery times:

  • Europe: 1–2 working days
  • North America: 2–3 working days
  • Asia-Pacific & Rest of World: 3–5 working days

Delivery times vary depending on location, customs clearance, and local courier performance.


💰 Taxes, Customs & Import Duties

International customers are responsible for any applicable taxes, customs charges, or import duties.
These are not included in our product or shipping prices.

Your courier will typically provide a secure payment link for any import charges once your parcel reaches customs.
If import fees are refused and the parcel is returned, we will issue a refund minus all incurred shipping and return costs.


📍 Using Your Own Courier

If you would prefer to arrange collection via your own courier (UK or international), please contact us before placing your order to coordinate collection from our Wisbech warehouse.


📝 Important Notes

  • Please ensure your delivery address and contact number are correct at checkout.
  • Undelivered parcels may be returned to us after a short holding period.
  • Redelivery or return fees may apply, even if your order originally qualified for free delivery.
  • By placing an order, you confirm your understanding and acceptance of this policy.

Additional information

Fluke 1746/ EUS Three-Phase Power Quality Logger – Choice of Kit

Fluke 1746/15/EUS, Fluke 1746/30/EUS, Fluke 1746/B/EUS