Fluke 1760 Three-Phase Power Quality Recorder

Fluke

£14,009.00 / £16,810.80 incl VAT

⚡ Fully compliant with IEC 61000-4-30 Class A standards
⚡ Made for use on utility and industrial power distribution systems
⚡ Customisable thresholds, algorithms and measurement slections
⚡ 8 input channels
⚡ Captures data on included 2GB SD card

Price Pledge
SKU: FLU-1760-BASIC Category: Brand:

Description

Fluke 1760 Three-Phase Power Quality Recorder

⚡ Please Contact us via email or telephone to find out the current lead time ⚡

Use the Fluke 1760 to constantly log power quality information from 8 separate input channels (connect 4 current/4 voltage or up to 8 voltage channels simultaneously).

Designed for use out in the field, the Fluke 1760 is rugged and reliable enough to withstand any kind of environment and is designed to be left constantly logging power information over a time period directly onto an SD card that’s included as standard with the tester. This information can then be downloaded once testing is completed and interacted with further via the use of an included software package.

The 1760 is designed to log a comprehensive range of values, including voltage events (dips, swells and interruptions) and can constantly log total harmonic distortion, voltage and current harmonics up to the 50th/interharmonics, frequency, unbalance, flicker, kWh, power factor, power (P, Q and S), current and voltage (via the use of included flexible current probes and voltage probes).

Key Features:

  • Fully compliant with IEC 61000-4-30 Class A standards
  • Made for use on utility and industrial power distribution systems
  • Customisable thresholds, algorithms and measurement slections
  • 8 input channels
  • Captures data on included 2GB SD card
  • 10MHz, 6000Vpk waveform capturing
  • Uninterrupted power supply
  • GPS time synchronisation
  • Further analysis using included software
  • Measures voltage events
  • Measures voltage and current
  • Measurements of Power, power factor and kWh
  • Flicker, unbalance, frequency measurements
  • Voltage and current harmonics to the 50th + interharmonics function
  • Total harmonic distortion
  • Mains signalling and trigged recording

Full List of Products Included:

  • Fluke 1760 Three-Phase Power Quality Recorder
  • 2GB SD Card
  • PQ Analyse Software on CD-ROM
  • Ethernet Cable
  • Crosslink Ethernet Cable
  • Mains Cable
  • Operational Manuals
  • Carrying Bag 4 x Voltage Probes
  • 4 x Current Probes
  • GPS Time Sync Receiver
Overview of Measurement Functions
Statistical Evaluation
 Power quality statistics according to EN50160 and DISDIP tables like ITIC, CEBEMA, ANSI
Event List
 Dips, swells and interruptions are detected and stored in the event list. Also any trigger which fires generates an event added to this list.
 The Event list shows the exact time when the event occurred as well as the duration and magnitude. Sorting by several attributes of these events is possible to select one for further root cause analysis.
 RMS values, transients and fast transients can be stored if a trigger fires.
Continuous Recording
 Fluke 1760 records rms values together with corresponding minimum and maximum values for:
 • Voltage
 • Current
 • Power P, Q, S
 • Power Factor
 • kWh
 • Flicker
 • Unbalance
 • Frequency
 • Harmonics/Interharmonics
 continuously with the following time aggregations:
 Day
 10 min
 Free Interval, e.g.: 15 min, 2h
Triggered Recordings
rms:  Aggregation time is adjustable between 10 ms (1/2 cycle), 20ms (1 cycle), 200ms (10/12 cycles) or 3 sec (150/180 cycles).
 Calculating rms values, Harmonics and Interharmonics is performed synchronous to the power frequency.
 Basic aggregation for harmonics and interharmonics is 200ms
Oscilloscope:  Sample rate is 10.24 kHz for all 8 channels
Fast Transients:  Sample rate is selectable from 100 kHz to 10 MHz for channel 1-4 FFT of Fast Transients
Mains Signalling
 Phases and N-conductor, Voltage and current
Online Mode
 Variable refresh rate. This feature allows verification of instrument set up and delivers a quick overview of oscilloscope, transients and events.

 

General Data
Intrinsic uncertainty
 refers to reference conditions and is guaranteed for two years
Quality system
 developed, manufactured as per ISO 9001: 2000
Environment conditions
Operating temp. range:  0 °C to +50 °C; 32 °F to +122 °F
Working temp. range:  -20 °C to +50 °C; -4 °F to +122 °F
Storage temp. range:  20 °C to +60 °C; -4 °F to 140 °F
Reference temperature:  23 °C ± 2 K; 74 °F ± 2 K
Climatic class:  B2 (IEC 654-1), -20 °C to +50 °C; -4 °F to +122 °F
Max. operating altitude:  2000 m: max. 600 V CAT IV*, power supply: 300 V CAT III 5000 m: max 600 V CAT III*, power supply: 300 V CAT II
* depending on sensor
Reference conditions
Environment temp.:  23 °C ± 2 K ; 74°F ± 2 K
Power supply:  230 V ± 10 %
Power frequency:  50 Hz / 60 Hz
Signal:  declared input voltage Udin
Averaging:  10 minute intervals
Housing
 insulated, robust plastics housing
EMC
Emission:  Class-A as per IEC/EN 61326-1
Immunity:  IEC/EN 61326-1
Power supply
Range:  AC: 83 V to 264 V, 45 to 65 Hz
 DC: 100 V to 375 V
Safety:  IEC/EN 61010-1 2nd edition
 300 V CAT III
Power consumption:  max. 54VA
Battery pack:  NIMH, 7.2 V, 2.7 Ah
 In case of a power supply failure an internal battery maintains the supply for up to 40 minutes. Afterwards, or in case of discharged accumulators the Fluke 1760 is turned off and continues the measurements with the latest settings as soon as the supply voltage returns. The battery can be replaced by the user.
Display
 Fluke 1760 features LED indicators for the status of the 8 channels, phase sequence, power supply (mains or accumulator), memory usage, time synchronization, and data transfer.
Power LED:  • Permanent light: normal power supply from mains.
 • OFF: supply via internal accumulator in case of a power failure.
Channel LEDs  3-color LEDs per channel for:
 • overload condition
 • under load condition
 signal level in nominal range
Data memory
 2 GB Flash memory depending on model
Memory model
 Linear
Interfaces
 Ethernet (100MB/s), compatible to Windows® 98/ME/NT/2000/XP RS 232, external modem via RS 232
Baud rate for RS 232
 9600 Baud to 115 kBaud
Dimensions
 325 mm x 300 m x 65 mm; 2.8 x 11.8 x 2.6 in. (H x W x D)
Weight
 appr. 4.9 kg; 10.8 lbs. (without accessories)
Warranty
 2 years
Calibration interval
 1 year recommended for Class-A, otherwise 2 years

 

Signal Conditioning
Range for 50 Hz systems
 50 Hz ± 15 % (42.5 Hz to 57.5 Hz)
Range for 60 Hz systems
 60 Hz ± 15 % (51 Hz to 69 Hz)
Resolution
 16 ppm
Sampling frequency for 50 Hz power frequency
 10.24 kHz, The sampling rate is synchronized to mains frequency.
Uncertainty for frequency measurements
 < 20 ppm
Uncertainty of internal clock
 < 1s / day
Measurement intervals
 Aggregation of the interval values as per IEC 61000-4-30 Class-A
Min-, Max-values:  Half cycle, e.g.: 10 ms rms values at 50Hz
Transients:  Sample rate 100 kHz to 10 MHz per channel
Harmonics
 as per IEC 61000-4-7:2002: 200 ms
Flicker
 as per EN 61000-4-15:2003: 10 min (Pst), 2 h (Plt)

 

Measurement Inputs
Number of inputs
 8 galvanically isolated inputs for voltage and current measurements.
Sensor safety
 up to 600 V CAT IV depending on sensor
Basic safety
 300 V CAT III
Nominal voltage (rms)
 100 mV
Range (peak value)
 280 mV
Overload capacity (rms)
 1000 V, continuously
Voltage rise rate
 max. 15 kV / µs
Input resistance
 1 MΩ
Input capacitance
 5 pF
Input filter
 Each channel is equipped with a passive low-pass filter, an anti-aliasing filter and a 16-bit A/D converter. All channels are sampled synchronously with a common quartz-controlled clock pulse.
 The filters protect against voltage transients and limit the signal rise rate, reduce high frequency components and especially the noise voltage above half the sampling rate of the A/D converter by 80 dB, thus achieving very small measuring errors in an exceptionally large amplitude range. This is also valid under extreme operating conditions like transient voltages at the output of converters.

 

Uncertainties
Uncertainty at reference conditions
 Uncertainty including the voltage sensors is in compliance with IEC 61000-4-30 Class-A. All voltage sensors are suitable for DC up to 5 kHz
With Sensor 1000 V  0,1% at Udin = 480 V and 600 V P-N
Sensor 600 V  0,1% at Udin = 230 V P-N
Intrinsic uncertainty for harmonics
 Class I as per EN 61000-4-7:2002
Reference conditions
 23 °C ± 2 K < 60 % rH; 74 °F ± 2 K < 60 % rH
 Warmed up instrument > 3h
 Power supply: 100 V to 250 V ac
Temperature drift
 100 ppm / K
Aging
 < 0.05 % / year
Common mode rejection
 > 100 dB at 50 Hz
Temperature drift
 Change of amplification through temperature: < 0.005 %/K
Aging
 Change of amplification due to ageing: < 0.04 %/year
Noise
 Noise voltage, input short-circuited: < 40 µV
DC
 ± (0.2% rdg + 0.1% sensor)