Product Details:

The Fluke 1663 – the new, improved version of the Fluke 1653B Multifunction Tester. The Fluke 1663 includes everything a professional electrical installer needs including a huge variety of different measurement functions, built-in memory storage, and download, and fast, easy-to-configure testing procedures.

Several new functions are included in 1663 which weren’t found on the original 1653B. These are:

  • Continuity checks at L-N, L-PE, and N-PE inputs
  • On/off switchable auto starts for RCD and loop testing
  • Z max memory
  • Heavy-duty mains cord with the single input connector

On top of these new functions you can also expect all of the typical measurements you’ll need such as voltage (AC/DC), frequency, wiring polarity, insulation resistance, loop/line resistance, prospective earth fault current (PEFC/IK), prospective short-circuit current (PSC/IK) and several RCD measurement modes such as RCD trip time, ramp test (RCD trip current) and more.

Key Features:

  • Suitable for testing smooth, DC-sensitive RCDs (Type B/B+)
  • True RMS AC/DC voltage measurements
  • Frequency measurements
  • Wiring polarity checker – detects broken PE and N wires
  • Insulation resistance measurements
  • Continuity and resistance measurements – includes motor winding testing with continuity test at 10mA
  • Loop and line resistance measurements
  • Prospective earth fault current (PEFC/IK) measurements
  • Prospective short-circuit current (PSC/IK) measurements
  • RCD trip time function
  • RCD trip current (ramp test)
  • Measure trip time and current for A/AC type RCDs in one test
  • RCD variable test current
  • Automatic RCD test sequence
  • Phase sequence test
  • Self-testing function
  • Illuminated display for use in different lighting conditions
  • Integrated memory for storing data
  • IR-USB interface for download to PC (requires the use of optional Fluke DMS or FlukeView Software packages to view data – sold separately)
  • Remote probe makes it easier to activate testing results without holding the tester
AC/DC Voltage (TRMS)
Range Resolution Input Impedance Overload Protection
500V 0.1V 3.3MΩ 660V rms
Continuity Testing (Rlo)
Range (Autoranging) Resolution Open Circuit Voltage
20Ω 0.01Ω >4V
200Ω 0.1Ω
2000Ω
Insulation Resistance Measurement (Riso)
Model Number Test Voltages
1662 100, 250, 500 and 1000V
1663/1664 FC 50, 100, 250, 500 and 1000V
Test Voltage Insulation Resistance Range Resolution Test Current
50V 20MΩ/50MΩ 0.01MΩ/0.1MΩ 1mA @ 50kΩ
100V 20MΩ/100MΩ 0.01MΩ/0.1MΩ 1mA @ 100kΩ
250V 20MΩ/200MΩ 0.01MΩ/0.1MΩ 1mA @ 250kΩ
500V 20MΩ/200MΩ/500MΩ 0.01MΩ/0.1MΩ/1MΩ 1mA @ 500kΩ
1000V 20MΩ/200MΩ/1000MΩ 0.01MΩ/0.1MΩ/1MΩ 1mA @ 1MΩ
Insulation Pretest
Insulation Safety Pretest Requires the unit to be connected to L, N and PE
Loop and Line Impedance (Zi)
Range Resolution
10Ω (Hi current mΩ mode) 20Ω/200Ω/2000Ω 1mΩ / 0.01Ω / 0.1Ω / 1Ω
RCD Testing
Model Number Types Tested
1662 AC, G, S, A/F
1663/1664 FC A/F, AC, B/B+, G and S
RCD Trip Time Test (ΔT)
Current Range Step Size Dwell Time Measurement Accuracy
Type G Type S
30 to 110% of RCD Rated Current 10% of index IΔN 300ms/step 500ms/step ±5%
Notes
30 % to 210 % for Type A IΔN = 10mA
20 % to 210 % for Type B
Specified trip current ranges (EN 61008-1):
50 % to 100 % for Type AC
35 % to 140 % for Type A (>10 mA)
35 % to 200 % for Type A (≤10 mA)
50 % to 200 % for Type B
Earth Resistance Test (RE) – Only Available On 1664 FC and 1663
Range Resolution Frequency Output Voltage
200Ω 0.1Ω 128Hz 25V
2000Ω 128Hz 25V
Phase Sequence Indication
Icon Range Display
Shows icon when active 100 to 500V 1-2-3 or 3-2-1
General Specifications
Dimensions 10cm (L) x 25cm (W) x 12.5cm (H)
Weight (Including Batteries) Approx 1.3kg
Battery Size 1.5V type AA (IEC LR6) x 6
Sealing IP40
Safety Complies with IEC/EN61010-1, UL61010, ANSI/ISA – s82.02.01 and CAN/CSA c22.2 No. 1010
Overvoltage CAT III 500V, CAT IV 300V
Performance EC/EN61557-1 to IEC/EN61557-7 and IEC/EN61557-10
  • Fluke 1663 Multifunction Installation Tester
  • CD and instruction manual for Fluke 1663 Multifunction Installation Tester
  • 6 x AA batteries
  • C1600 hard carry case
  • Zero adapter
  • Heavy duty mains cord
  • Standard test lead set
  • Padded carrying waist and neck strap
  • Remote control probe
  • Fused test probe set
  • Fluke 1663 Quick reference guide
  • Fluke calibration certificate