Kewtech SMARTPAT Professional Downloadable PAT Testing Kit


£789.00 / £946.80 incl VAT
- Complete PAT testing kit – Bluetooth SMARTPAT tester with labels, log book & essential test adaptors
- Downloadable results via the free KEWPAT app (Android & iOS) or use manually
- Battery or mains powered with over 1500 tests per charge
- Automatic PASS/FAIL testing for Class I & II appliances, including 110V & 230V
- Includes 2 pass label rolls, 1 fail roll, A4 PAT log book & specialist adaptors
In stock (can be backordered)
Description
Kewtech SMARTPAT Professional Downloadable PAT Testing Kit
Bluetooth PAT Tester + Labels, Log Book & Test Adaptors
The Kewtech SMARTPAT Complete PAT Testing Kit is a professional-grade solution designed to make Portable Appliance Testing faster, simpler, and more efficient. Combining Kewtech’s innovative SMARTPAT Bluetooth PAT tester with essential labelling, logging, and adaptor accessories, this kit provides everything needed to carry out compliant PAT testing straight out of the box.
The SMARTPAT can be operated manually or via the free KEWPAT app on Android and iOS, allowing users to download results, manage appliance registers, and customise test sequences. With both battery and mains operation, it is ideal for mobile testers, contractors, and facilities teams working across multiple sites.
SMARTPAT Tester Highlights:
Bluetooth-enabled PAT tester with app-controlled or manual operation
Stores and downloads test results via the KEWPAT app
Performs over 1500 tests per charge
Automatic PASS / FAIL indication on a clear backlit display
Automatic Class I and Class II test sequences
200mA earth bond testing (IT safe)
250V & 500V insulation resistance testing
Substitute leakage testing at 110V and 230V
Live run leakage testing at 110V and 230V
Portable RCD testing at 10mA and 30mA
Extension lead and appliance pre-check testing
Fast test lead nulling for improved accuracy
What’s Included:
Kewtech SMARTPAT Tester: (Includes: Mains lead, Earth continuity lead with probe/clip, Nulling pin, and Extension lead adapter).
2 x Leaderman PAT Pass Label Rolls: (250 labels per roll / 500 total).
1 x Leaderman PAT Fail Label Roll: (250 labels per roll).
1 x Leaderman LDM-PR PAT Report Pad: A4 log book with 40 NCR (duplicate) sheets; capacity for 880 test results.
1 x Leaderman 110V 16A Adaptor: Yellow socket to 13A mains plug for industrial equipment testing.
1 x Leaderman Cloverleaf Adaptor: IEC C13 to C6 adaptor for testing laptop mains leads.
Technical Specifications
Test Functions
Appliance status pre-check
PASS / FAIL indication (Green / Red screen)
Fast continuity test
5-second continuity test
Insulation testing at 250V & 500V
Substitute leakage testing
110V & 230V run / leakage testing
Extension lead testing (with L–N insulation test)
PRCD testing without tripping installed RCDs
Test lead nulling
Backlit display
Supplied Accessories
Mains lead
Earth continuity lead with probe & crocodile clip
Extension lead adaptor
Carry bag with shoulder strap
Quick start manual
End-of-line calibration certificate
Protective Conductor Resistance Test
Measuring range: 0.00 – 20.00 Ω (NULL value included)*
Over-range indication: > 20.00 Ω
Resolution: 0.01 Ω
Open-circuit voltage: 5 V ±0.4 V DC
Measuring current: 200 mA DC (nominal)
Accuracy: ±3% rdg ±5 dgt
* Resistances exceeding 3 Ω cannot be cancelled by the NULL function.
Insulation Test (Substitute Leakage – L to N)
Test voltages: 250V / 500V
Mains Voltage Measurement
Display range: 30 – 270 V
Hi / Lo indication:
< 30 V: No voltage indication
270 V: 270 V displayed
Resolution: 1 V
Accuracy: ±3% rdg ±5 dgt
Run / Leakage Test (110V & 230V)
| Parameter | Load Current | Leakage Current |
|---|---|---|
| Measuring range | 0.10 – 13.00 A rms | 0.10 – 20.00 mA rms |
| Display range | 0.00 – 13.00 A | 0.00 – 20.00 mA |
| Over-range indication | > 13.00 A | > 20.00 mA |
| Resolution | 0.01 A | 0.01 mA |
| Accuracy | ±10% rdg ±5 dgt | ±3% rdg ±5 dgt |
Mains voltage range: 100 – 253 V / 50 Hz
Maximum rating: 3 kVA max / 15 sec continuous
RCD / PRCD Testing
Rated voltage: 230 V (-15% to +10%) / 50 Hz
Rated test currents: 10 mA / 30 mA
Test duration:
×1: 0.0 – 500.0 ms
×5: 0.0 – 40.0 ms
Test current accuracy: 2% – 8%
Operating time accuracy:
±2 ms (≤ 40 ms)
±8 ms (> 40 ms)
Click Here – SMARTPAT-Data-sheet-2025
Kewtech SMARTPAT Tester: (Includes: Mains lead, Earth continuity lead with probe/clip, Nulling pin, and Extension lead adapter).
2 x Leaderman PAT Pass Label Rolls: (250 labels per roll / 500 total).
1 x Leaderman PAT Fail Label Roll: (250 labels per roll).
1 x Leaderman LDM-PR PAT Report Pad: A4 log book with 40 NCR (duplicate) sheets; capacity for 880 test results.
1 x Leaderman 110V 16A Adaptor: Yellow socket to 13A mains plug for industrial equipment testing.
1 x Leaderman Cloverleaf Adaptor: IEC C13 to C6 adaptor for testing laptop mains leads.
You may also like…
- Out of StockSale!
- Socket Testers
Kewtech LOOPCHECK 107 Mains Socket Tester
- Original price was: £53.00.£36.00Current price is: £36.00. / £43.20 incl VAT
- Read more
- PAT Testers
Kewtech SMARTPAT Bluetooth PAT Tester
- £734.00 / £880.80 incl VAT
- Add to basket
- Sale!
- PAT Printers & Scanners
Kewtech KEW80L Bluetooth PAT Label Printer Including 2 Rolls of Labels
- Original price was: £229.00.£159.00Current price is: £159.00. / £190.80 incl VAT
- Add to basket